CIRCUIT BREAKER >> ELCB/RCCB/RCD
ID
 

                     

                                      2P                                                         4P

Application

ID RCCB is in conformity with the standard of IEC61008. The RCCB can cut off the fault circuit immediately on the occasion of shock hazard or earth leakage of trunk. Thus, it is suitable to avoid the shock hazard and fire caused by earth leakage.
The RCCB is mainly suitable for use in varieties of plants and enterprises, building construction 1 phase 230V and 3 phase 400V 50/60Hz. RCCB is not suitable for use on DC pulse system.
Specifications
Number of Poles
2P, 4P
Rated Current (A)
16, 20, 25, 32, 40, 50, 63, 80, 100
Rated Residual Operating Current ()(mA)
10, 30, 100, 300, 500
Rated Voltage (V)
AC 230/240
AC 400/415
Residual Operating Current Scope
0.5~
Residual Current Off-time
¡Ü0.1S
Short Circuit Capacity (Icu)
3000A
Endurance
4000
Protection Degree
IP20
Normal Operation and Mounting Requirement
£¤Circumstance temperature -5iC~+40iC, average temperature not exceeding 35iC.
£¤Altitude above sea level less than 2000m.
£¤Humidity not exceeding 50% at 40iC and not exceeding 90% at 25iC.
£¤Installation class II or III.
£¤Pollution class II.
£¤Installation method DIN Rail mounting type.
£¤The external magnetism shall not be more than 5 times of terrestrial one.
£¤Product shall be installed vertically at the place where there shall be no severe impact and vibration. The product is switched on when the handle is at upperposition.
Operation Principle
Overall And Mounting Dimensions (Unit: mm)